Powerware 9315 Manual do Utilizador Página 123

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 154
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 122
INSTALLATION REFERENCE
EATON Powerware
®
9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com
A-13
Table E. Input/Output Ratings and External Wiring Requirements (PW9315-625/400, PW9315-625/450, PW9315-625/500, and PW9315-625/562)
Basic Unit Rating
PW9315-625/400 and PW9315-625/500 at 0.8 Lagging pF Load
PW9315-625/450 and PW9325-625/562 at 0.9 Lagging pF Load
Units Rating 50/60 Hz
kVA/kW 500/400 500/450 625/500 625/562
Input and Output Voltage Volts 400 400 400 400
AC Input to UPS Rectifier (0.95 Min. pF)
(3) Phases, (1) Neutral, (1) Ground
A
Amps* 880 910 1100 1138
Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current
AWG or kcmil
(each)
350
(4)
400
(4)
600
(4)
700
(4)
AC Input to MBC (UPS Bypass)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
DC Input from Battery to UPS
(1) Positive, (1) Negative
C
Vdc
Amps @ (2.0V/cell)
384
1096
384
1234
384
1371
384
1542
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
400
(4)
500
(5)
400
(5)
700
(5)
AC Output to Optional SBM
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
E
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps 722 722 902 902
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
300
(4)
300
(4)
500
(4)
500
(4)
NOTE Callout letters A, B, C, D, and E map to Figure A‐8.
Vista de página 122
1 2 ... 118 119 120 121 122 123 124 125 126 127 128 ... 153 154

Comentários a estes Manuais

Sem comentários