Vista de página 54
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
164201546---2 1 of 1
PHYSICAL FEATURES AND REQUIREMENTS
031505A
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com
A-5
1. The UPS Sidecar equipment operating environment must meet the weight requirements
shown in the applicable Powerware 9390 installation and operation manual, listed in
paragraph 1.5, plus 150 pounds for the UPS Sidecar. Size requirements are shown in
Drawing 164201546---8 starting on page A---68.
2. Donottiltcabinetsmorethan10˚ during handling.
3. Dimensions are in millimeters (inches).
4. The clearances required around the UPS Sidecar cabinet are shown in Table A.
Table A. UPS Sidecar Cleara nces
From Top of Cabinet Minimum clearance over the UPS Sidecar is
457.2 mm (18) for ventilation
From Front of Cabinet 914.4 mm (36)workingspace
F rom Back of Cabinet None Required
F rom Right Side of Cabinet None Required
5. The basic environmental requirements for operation of the UPS Sidecar are:
Ambient Temperature Range: 0 --- 4 0˚C ( 3 2 --- 1 0 4 ˚F)
Recommended Operating Range: 20---25˚C ( 6 8 --- 7 7 ˚F)
Maximum Relative Humidity: 95% noncondensing