POWER WIRING INSTALLATION NOTES
061507
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
D
164201546---4 2 of 10
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com
A-18
Ta b l e C. INPUT/OUTPUT Ratings & External Wiring Requirements for
Po werware 9390 UPS Sidecar ( Maintenance Bypass) 480/480V
Units Rating 50/60 Hz
Basic Unit Rating
UPS kVA 20 30 40 50 60 80 100 120 160
Input and Bypass Input
Output
VOLTS
VOLTS
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
AC Input to Maintenance
Bypass (without BIB or RIB, or
dual feed with BIB and RIB)
(3) Phases, (1) Ne u tral--- if required,
(1) Ground
A
AMPS 24 36 48 60 72 96 120 144 193
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
AC Input to Maintenance
Bypass (single feed with BIB, or
single feed with BIB and RIB)
(3) Phases, (1) Ne u tral--- if required,
(1) Ground
A
AMPS 30 40 55 67 80 105 130 160 210
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
AC Input to Optional RIB
(3) Phases, (1) Ground
B
AMPS 30 40 55 67 80 105 130 160 210
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
AC Output to Critical Load
F ull Load Current
(3) Phases, (1) Neutral --- if required,
(1) Ground
C
AMPS 24 36 48 60 72 96 120 144 193
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
NOTE Callout letters A, B, and C map to drawing 164201546 ---3, sheets 1 of 11,
2of11,3of11,4of11,5of11,6of11,7of11,8of11,and9of11.