Powerware 9330 Manual do Utilizador Página 184

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 246
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 183
DESCRIPTION:
DATE:
DRAWING NO:
13 of 17
SHEET:
REVISION:
F
111501
POWER WIRING INSTALLATION NOTES
164201300---1
A --- 1 4
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table S. Power Cable Conduit Requirements Powerware 9330 (20 kVA)
Powerware
System
Voltage Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
(inches)
Number of
Conduits
AC Input to UPS
(A,B,C,Gnd)
4 1 1
9330-20/20
208
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 1 1
A
C
Output
(A,B,C,Neut,Gnd)
5 1 1
AC Input to UPS
(A,B,C,Gnd)
4 1/2 1
9330-20/20
480
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 3/4 1
C
Output
(A,B,C,Neut,Gnd)
5 3/4 1
AC Input to UPS
(A,B,C,Gnd)
4 1/2 1
9330-20/20
600
AC
AC Input to Bypass
(A,B,C,Neut,Gnd)
5 1/2 1
C
Output
(A,B,C,Neut,Gnd)
5 1/2 1
9330---20/20
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3 3/4 1
Vista de página 183
1 2 ... 179 180 181 182 183 184 185 186 187 188 189 ... 245 246