POWER WIRING INSTALLATION NOTES
A --- 1 8
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
16. Output overcurrent protection and output disconnect switch are to be provided by the
user. Table W lists the maximum rating for output circuit breakers satisfying the criteria for
both.
Table W. Maximum Output Circuit Breake r Ratings
Output Voltage Rating
owe
wa
e
s
em
208V 480V 600V
9330---20/10 35 15 15
9330---20/15 60 25 20
9330---20/20 70 30 25
9330---40/25 90 40 30
9330---40/30 110 45 40
9330---40/35 125 60 45
9330---40/40 150 60 50
17. Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at the computed voltage.