FERRUPS®Uninterruptible Power SystemsFE or QFE 500VA to 18KVA 50/60 HzUSER MANUAL FSS-0342JListed Models Available

Página 2 - IMPORTANT SAFETY INSTRUCTIONS

Page 7CAUTIONTo avoid possible equipment damage or personal injury, assume that FERRUPS’ terminals or receptaclesmay have AC voltage present any time

Página 3 - Table of Contents

Page 84To start FERRUPS on battery power, use thekey toturn on the On/Off switch. After a brief self-check, the yellow BATTERY POWER light andthe gree

Página 4 - Introduction

Page 96FERRUPS units with receptacles on the back:Plug the equipment you want to protect into theFERRUPS’ receptacles. Then, switch on yourequipment.

Página 5

Page 108Please fill out the Warranty Registration Card in this manual and return it to Best Power. This cardhelps Best Power’s Worldwide Service when

Página 6 - Section 200: Startup

Page 11Section 300: OperationThis section will describe how FERRUPS works. We’ll discuss the meaning of the front panel lights and describehow to use

Página 7

Page 12302 How to Use the Control PanelThe control panel comes with all FE/QFE 4.3KVA to 18KVA models. If you have an FE/QFE 500VA to3.1KVA, you may h

Página 8

Page 13How to Enter PasswordsBefore you can change some parameter values, you must enter a password. (The instructions below describe howto display an

Página 9 - FERRUPS Back View

Page 14How to Lock and Unlock the Control PanelYou may need to disable (lock) your control panel if you want to limit its use. When you disable the co

Página 10

Page 15303 Automatic System TestFERRUPS regularly tests its memory, batteries and inverter to make sure they will perform when you needthem. (The fac

Página 11

Page 16Letter AudioCodeAlarm Message What It Means What To DoA – Low Battery The battery charge is low becausethe system was running on batterypower,

Página 12

IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONS — This manual contains important instructions for your UPS.How to Use This ManualYour FERRUPS is

Página 13

Letter AudioCodeAlarm Message What It Means What To DoPage 17M – – Check Battery The batteries have failed theautomatic system test.Phone Best Power’s

Página 14 - Section 300: Operation

1If you change parameter 39 to “Yes,” a User password is required for changes. 2 On a FERRUPS control panel, you can display the Ambient Temp

Página 15 - How to Change Operating Modes

Number Sample Display Password TerminalName(Short Form)ExplanationPage 1914 14 XfmrTemp 28c Change NotAllowedxfmrtemp(xt)The temperature of the transf

Página 16 - How to Enter Passwords

Page 20306 How to Read the Alarm and Inverter LogsYour FERRUPS makes an entry in its logs every time it sounds an alarm or switches to inverter (batte

Página 17

Page 21Each entry includes four pieces of information: the inverter code, the date (month/day) of the inverter run, thetime (in 24-hour time) and the

Página 18 - 303 Automatic System Test

Page 22307 If You Have an Extended Power OutageIf your power is out for an extended time, your FERRUPS will continue to provide power for your equipme

Página 19

Page 23Units with a Break-Before-Make Bypass Switch (see the label on the side of the switch):Shut down your protected equipment; then, turn the bypas

Página 20 - 305 Parameter Table

Page 24Section 400: CommunicationFERRUPS is capable of full-duplex communication, so it can communicate with a computer, a Local AreaNetwork, or a mul

Página 21

Page 25Figure 401401 Connecting a Terminal or Computer to the RS232 Port CAUTIONDo not make connections to the RS232 communication port if FERRUPS is

Página 22

Page 26Figure 402Computer DB25 to UPS2. Connect the cable from the RS232 port on the back of the FERRUPS to the serial port on your terminal orcompute

Página 23

Table of ContentsIntroduction...1001 If You Have a Problem or a Question...

Página 24

4If you change parameter 39 to “Yes,” this command requires the User password.Page 27To do this Use this key sequenceDelete last character typed.

Página 25 - How to Shut Down Your FERRUPS

Command Short Form Password Function 4If you change parameter 39 to “Yes,” this command requires the User password.Page 28delay dl NoneDelays next

Página 26

Command Short Form Password FunctionPage 29program pr DependsonparameterpasswordLets you set the value of any parameter. You must enter theappropriate

Página 27 - Section 400: Communication

Page 30403 Remote Monitoring and Remote ShutdownMonitoringAlarm Signal Contacts:These are relay contacts (rated at 25V AC/DC and 250 mA) that changest

Página 28 - Computer DB9 to UPS

Page 31Section 500: Maintenance and ServiceIn this section, we’ll look at the kind of maintenance your FERRUPS needs and how to contact Best Power’sWo

Página 29 - Computer DB25 to UPS

Page 32Section 600: Specifications601 Specification Table: Standard Product — FE and QFE 500VA-3.1KVAModel 500VA/350W700VA/500W850VA/600W1.15KVA/800W1

Página 30

Page 33602 Specification Table: Standard Product — FE and QFE 4.3KVA-18KVAModel 4.3KVA/3kW 5.3KVA/3.7kW 7KVA/5kW 10KVA/7.5kW 12.5KVA/10kW 18KVA/15kWAC

Página 31

Page 34603 AC Output with Nominal Input Power and Loads (Protected Equipment)Voltage Regulation: FERRUPS provides ±3% load regulation. Total voltage r

Página 32

Page 35Ventilation Requirement: Clean, dust-free air, free of corrosive chemicals or other contaminants must beavailable. FERRUPS uses internal fans t

Página 33 - Remote Shutdown

Page 36Section 700: WarrantyLIMITED TWO YEAR WARRANTYStandard Warranty For All PurchasesBEST POWER, a division of General Signal Power Systems, Inc. (

Página 34 - 502 Service and Support

Page 1IntroductionWelcome to the growing FERRUPS family. FERRUPS represents a breakthrough in the design of advanced, on-line uninterruptible power sy

Página 35 - Section 600: Specifications

Page 37LIMITED WARRANTYTransient Voltage Surge Suppression Circuitry(For U.S. and Canadian Purchasers Only)BEST POWER, a division of General Signal Po

Página 36

Page 38Section 800: OptionsBest Power offers many options for your FERRUPS. The list below describes these options; if you would likemore information,

Página 37 - 606 Environment

Receptacles:The following output receptacles are available for new units. NOTE: 5-15R receptacles arestandard for the FE500, 700, and 850VA and 1.15 a

Página 38 - 607 Protection

For Users in the United States OnlyThis equipment has been tested and found to comply with the limits for a Class A digital device, pursuant toPart 15

Página 39 - Section 700: Warranty

ALARM AUDIO CODEA– Low Battery K –  – High Transformer TempB–   Near Low Battery L –  Check ChargerC–  – High Battery M – – Check BatteryD–

Página 40

Page 2Section 100: Identifying Your FERRUPSFERRUPS units come in different sizes. This section will help you choose the startup section for your model

Página 41 - Section 800: Options

Page 3Section 200: StartupThis section provides step-by-step instructions on starting your FERRUPS. We’ll explain how to turn on DC andAC power and ho

Página 42 - QA QG

Page 4CAUTIONTo avoid possible equipment damage or personal injury, assume that AC voltage is present at theFERRUPS terminals or receptacles any time

Página 43

Page 54FERRUPS units with receptacles on the back:Plug the equipment you want to protect into theUPS’ receptacles. (If you have a 50 Hz model,use the

Página 44 - ALARM AUDIO CODE

Page 6203 Startup: FE and QFE 4.3KVA to 18KVAMake sure the temperature is 0 to 40 Celsius (32 to 104 Fahrenheit). The relative humidity must be 0-