Installation/OperationManualMaintenance BypassModule30--160kVA164201177 Rev. C9315
6Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Preparing the SiteFor the MBM to operate at peak efficiency, the installati
7Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Inspecting and Unpacking the Maintenance Bypass ModuleThe first task in p
8Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 0415001. Carefully inspect the outer packaging for evidence of damage during tran
9Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Unloading the MBM from the PalletThe MBM pal l et consists of four metal
10Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500FRONT SIDESUPPORTSUPPORT112JACKING BOLTFLOORPROTECTOR12DOORREARSUPPORT(USE
11Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Installing and Wiring theMaintenance Bypass ModuleWhen the maintenance b
12Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Refer to the following while installing the MBM:· Dimensions in this manua
13Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500The recommended location, for the Maintenance Bypass Module, is as close
14Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500This Page Intentionally Left Blank.
15Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Maintenance Bypass Module OperationThis chapter provides preliminary che
iiPo werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500--------------------------------------------------------------------------
16Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500MBM Operation Without Kirk Key InterlocksThe following transfer sequence i
17Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500MBM Operation With Kirk Key Interlocks (Optional)The following transfer
18Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500From Maintenance Bypass to UPS Bypass:1. Confirm BIBs, if installed, are c
19Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500MaintenanceMaintenance should be scheduled on a periodic basis, recommen
20Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500This Page Intentionally Left Blank.
A --- 1Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Appendix A --- Customer InformationThe information in this appendix
DESCRIPTION:DATE:DRAWING NO:1of4INSTALLATION NOTESSHEET:REVI SI ON:C164201177---1041500A --- 2Po werware 9315 Maintenance Bypass Module 30-160kVA16420
DESCRIPTION:DATE:DRAWING NO:2of4INSTALLATION NOTESSHEET:REVI SI ON:C164201177---1041500A --- 3Po werware 9315 Maintenance Bypass Module 30---160kVA164
DESCRIPTION:DATE:DRAWING NO:3of4INSTALLATION NOTESSHEET:REVI SI ON:C164201177---1041500A --- 4Po werware 9315 Maintenance Bypass Module 30-160kVA16420
DESCRIPTION:DATE:DRAWING NO:4of4INSTALLATION NOTESSHEET:REVI SI ON:C164201177---1041500A --- 5Po werware 9315 Maintenance Bypass Module 30---160kVA164
iiiPo werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Table of Contents1 Introduction 1...
DESCRIPTION:DATE:DRAWING NO:1of2INSTALLATION NOTESSHEET:REVI SI ON:C164201177---1041500A --- 6Po werware 9315 Maintenance Bypass Module 30-160kVA16420
DESCRIPTION:DATE:DRAWING NO:2of2INSTALLATION NOTESSHEET:REVI SI ON:C164201177---1041500A --- 7Po werware 9315 Maintenance Bypass Module 30---160kVA164
A --- 8Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Ta bl e C -- 1 . Po wer C ab l e Te rm in at io nsWith Optional BIB W
A --- 9Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Table C-- 2. Control Wiring Requirements and Termination Requiremen
A --- 1 0Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Dimensions are in millimeters (inches)DESCRIPTION:DATE:DRAWING NO:1
A---11Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500DESCRIPTION:DATE:DRAWING NO:2of3SHEET:REVI SI ON:A164201177---208049
A --- 1 2Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Dimensions are in millimeters (inches)DESCRIPTION:DATE:DRAWING NO:3
A---13Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500DESCRIPTION:DATE:DRAWING NO:1of1TYPICAL UPS SYSTEM WITH MBMSHEET:REV
A --- 1 4Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Read and understand the following notes while planning your install
A---15Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Read and understand the following notes while planning your installa
ivPo werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500List of FiguresFigure 1. Typical 30---160kVA MBM with Isolation Transforme
A --- 1 6Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Read and understand the following notes while planning your install
A---17Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Read and understand the following notes while planning your installa
A --- 1 8Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Read and understand the following notes while planning your install
A---19Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Read and understand the following notes while planning your installa
A --- 2 0Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500DESCRIPTION:DATE:DRAWING NO:1of4SHEET:REVI SI ON:A164201177---10LIN
A---21Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500DESCRIPTION:DATE:DRAWING NO:2of4SHEET:REVI SI ON:A164201177---10LINE
A --- 2 2Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500DESCRIPTION:DATE:DRAWING NO:3of4SHEET:REVI SI ON:A164201177---10LIN
A---23Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500DESCRIPTION:DATE:DRAWING NO:4of4SHEET:REVI SI ON:A164201177---10LINE
A --- 2 4Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500This Page Intentionally Left Blank.
1Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500IntroductionThe Powerware 9315 Maintenance Bypass Module (MBM) is afloor-
2Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500Using This ManualThis manual contains installation and operation procedures
3Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500For More InformationFor more information on the installation and operatio
4Po werware 9315 Maintenance Bypass Module 30-160kVA164201177 Rev. C 041500This Page Intentionally Left Blank.
5Po werware 9315 Maintenance Bypass Module 30---160kVA164201177 Rev. C 041500Getting StartedThis section describes how to install the Powerware 9315 M